The Columbus Utilities detected measurable quantities of the 20 parameters listed in the following table. An additional 51 parameters were tested for, but were not present in quantities that were detectable. This is done to ensure that your water is as safe as is technologically possible. A list of all regulated chemicals is available upon request.
National Primary Drinking Water Parameters
Maximum Contaminant Level(MCL)
Water Plant 1
Water Plant 2
CLARITY (NTU)
Turbidity Ground Water
5
0.06
0.02
MICROBIOLOGICAL (Percent Positive)
Coliform
Presence/Absence
Absent
Absent
INORGANIC COMPOUNDS (mg/L)
Barium
2
0.054
0.054
Fluoride (Adjusted)
4
1.21
1.06
Nickel
0.1
<0.003
<0.003
NITRATES AND NITRITE (mg/L)
Nitrate (as N)
10
<0.50
4.29
LEAD AND COPPER (mg/L)
Lead (Action Level)
0.015
0.004
0.004
Copper (Action Level)
1.300
0.010
0.049
ORGANIC COMPOUNDS (mg/L)
Total Trihalomethanes
80
15.38
16.58
ADDITIONAL PARAMETERS (Unit is mg/L unless specified)
Alkalinity
280
230
Calcium
104
96
Conductivity (umhos/cm)
626
579
Hardness as CaC0 3
356
312
Hardness as CaC0 3 (Grains/gallon)
21
18
Iron
0.3
0.10
0.03
Magnesium
32
28
Manganese
0.05
<0.05
<.05
pH (pH Unit)
6.5 - 8.5
7.4
7.6
Silica
9.76
9.99
Sodium
19.60
9.22
Sulfate
250
56.3
53.5
Total Dissolved Solids
432
381
Zinc
5
<0.014
<0.007
TURBIDITY RESULTS
Plant 1
MCL
MCLG
level found
range
sample date
violation
typical source
Turbidity
TT=5NTU
-
2.78
-
6/13/2005
No
soil runoff
TT= percentage of samples<0.5 NTU
99.98 %
-
Plant 2
MCL
MCLG
level found
range
sample date
violation
typical source
Turbidity
TT=5NTU
-
1.66
-
1/18/2005
No
soil runoff
TT= percentage of samples<0.5 NTU
99.99 %
-
KEY TO ABBREVIATIONS
mg/L = milligrams per Liter
mrem/year = millirems per year
EXPLANATIONS
One milligram per liter is the same as one part per million or one dollar out of one million dollars .